What is Tan Delta Test : Its Principle and Modes

Author: Helen

May. 13, 2024

51 0 0

What is Tan Delta Test : Its Principle and Modes

We are aware that transformers find extensive use across numerous sectors. Therefore, it is vital to delve deeper into transformer maintenance, which includes oil tests, equipment testing, and other procedures. Specific focus is required for dissolved gas analysis, which evaluates the overall electrical state of a transformer. Since transformer oil plays a critical role in circuit breakers, cables, and switches, assessing its condition is essential. This is due to the fact that oil enhances dielectric properties, and the Tan Delta Test is employed to determine the health of transformer oil. This article offers an in-depth look at what a Tan Delta Test is, its principle, and the various methods and modes used

Click here to get more.


Understanding Tan Delta Test

The Tan Delta Test, also referred to as Dielectric Dissipation, Loss Angle, or Power Factor testing, is conducted to evaluate the quality of insulating oil. This test is performed at two different temperatures, and the results are compared to assess the quality of the coil's insulation. If the results are satisfactory, the oil continues to be used; if not, the oil is either replaced or adjusted.

Objective

The primary purpose of the tan delta test is to ensure the transformer operates safely and reliably. By calculating the dissipation factor and capacitance values, it reveals the insulation condition in the bushings and windings of the transformer.

Changes in capacitance values, for instance, can indicate partial breakdowns in bushings or automatic winding movements. Insulation degradation and equipment aging convert increased energy levels into heat, which is measured as the dissipation factor.

The tan delta testing method allows for the identification of aging factors and the implementation of corresponding actions in a timely manner.

Principle Behind Tan Delta Test

A pure insulator connected between the earth and the line functions like a capacitor. In an ideal insulator, where the insulating material is entirely pure, the current flow through the material is purely capacitive. The insulator does not have any resistive element, and hence, no impurities exist in the insulating material. The tan delta test circuit diagram is depicted as follows:

In a purely capacitive material, the current leads the voltage by 90 degrees. In reality, insulating materials, due to aging and contamination from moisture and dirt, become conductive. These contaminants create a path for current, resulting in a leakage current with resistive elements.

Thus, for a high-quality insulator, the resistive element of the leakage current is minimal. The insulator's quality can be gauged by the ratio of its resistive element to capacitive element, known as tanδ or tan delta, also referred to as the dissipation factor. This can be observed from the vector diagram below.

Here, the x-axis represents the system voltage level, which is the resistive element of the leakage current (IR). The capacitive element of the leakage current (IC) leads by 90 degrees and is represented on the y-axis.

The overall leakage current (IL) is given by IL(IC + IR)

From the diagram, tanδ is (IR /IC)

tanδ =  (IR /IC)

Steps in Tan Delta Testing

The following steps outline the method of tan delta testing:

  • Separate the required components such as cables, potential transformers, bushings, current transformers, and windings from the system.
  • Apply a minimal frequency test voltage to the equipment to be analyzed.
  • Initially, normal voltage levels are applied. If the tan delta values are acceptable at this level, the test voltage is increased to twice the applied voltage.
  • The tan delta values are recorded by the tan delta controller.
  • A loss angle analyzer is connected to the tan delta measuring device to compare tan delta values at different voltage levels, providing accurate results.

Testing should be conducted at minimal frequency levels.

Low-frequency testing is recommended because higher applied voltages reduce the capacitive reactance of the insulator, increasing the capacitive current component. The resistive component is practically constant and based on the applied voltage and the insulator’s conductivity.

At higher frequency levels, the capacitive current increases, raising the total current amplitude. Thus, the power required for the tan delta test also increases, making low-frequency tests necessary to limit power constraints during dissipation factor analysis.

Interpreting Test Results

There are primarily two ways to assess the insulation condition during tan delta testing. The first involves comparing past test results to identify insulation degradation due to aging. The second is assessing the insulation behavior directly from the tanδ value without referring to past results.

If the insulation results are good, the loss factor values remain consistent across different test voltages. If not, the tanδ values increase at higher voltage levels, indicating a higher resistive current component in the insulation. These values can be compared with past test results to decide whether to replace the equipment.

Modes of Tan Delta Testing

There are three main test modes for the tan delta measurement:

  • GST Guard – Measures current leakage to the ground and excludes leakage through red or blue leads. When using UST mode, ground is considered as guard since grounded edges are not measured. Only current through blue or red leads is measured, bypassing the ground lead to the AC source.
  • UST Mode – Used to measure insulation between ungrounded leads. The specific insulation part is isolated for individual analysis.
  • GST Mode – Calculates total current leakage through all paths, providing a comprehensive measurement of current, capacitance, UST and GST guards, and loss in watts, which should equal GST parameters.

If the sum of GST Guard and UST is not equal to GST parameters, it indicates an issue with the test setup or terminal design.

You will receive exemplary service from Hengfeng.

Additional resources:
The Ultimate Guide to Choosing tan delta kit

Overall, this is a detailed overview of the Tan Delta Test. We have covered what the tan delta test is, its principle, objectives, methods, and procedures. Additionally, you will learn about LV to earth test, HV to earth test, and LV-HV tan delta testing techniques.

Understanding the Difference: Tan Delta Test vs. Megger ...

Understanding the Difference: Tan Delta Test vs. Megger Test

Maggie Lee

·

Follow

3 min read

·

Feb 21, 2024

--

When it comes to assessing the health and integrity of electrical insulation systems, two common methods employed are Tan Delta Test and Megger Test. Each serves a distinct purpose in detecting potential faults or weaknesses within electrical systems, offering valuable insights to engineers and technicians. In this comprehensive guide, we delve into the nuances of these tests, elucidating their differences, applications, and benefits.

Tan Delta Test: Unveiling the Power of Dielectric Dissipation

The Tan Delta Tester also known as the Dissipation Factor Test, is a sophisticated diagnostic technique used to evaluate the condition of insulation in high-voltage apparatus. It operates on the principle of measuring the dielectric dissipation factor or tan delta (δ), which signifies the energy loss within the insulation material. By subjecting the insulation to a high-frequency voltage, this test can discern subtle defects such as moisture ingress, contamination, or aging effects.

How Tan Delta Test Works

During the Tan Delta Test, a precision instrument applies a sinusoidal voltage signal to the insulation under test while simultaneously measuring the current and phase angle between voltage and current waveforms. The tangent of the phase angle yields the tan delta value, indicating the level of energy dissipation within the insulation. A high tan delta value suggests significant losses, indicative of potential insulation degradation.

Applications and Significance

Tan Delta testing is indispensable in assessing the condition of critical assets such as transformers, cables, generators, and bushings. It offers precise insights into the insulation’s health, enabling proactive maintenance strategies and preventing catastrophic failures. By detecting early signs of deterioration, Tan Delta testing facilitates timely interventions, prolonging the lifespan of electrical equipment and ensuring operational reliability.

Megger Test: Evaluating Insulation Resistance with Precision

In contrast, the Megger Test, also referred to as Insulation Resistance Test, focuses on assessing the electrical resistance of insulation materials. It is primarily utilized to detect insulation defects, such as cracks, voids, or contamination, by measuring the resistance to current flow across the insulation.

Operation of Megger Test

During a Megger Test, a high-voltage DC source is applied to the insulation under test, while the Megger instrument measures the resulting current flow. By analyzing the ratio of applied voltage to the measured current, the test determines the insulation resistance in ohms. A high resistance value signifies intact insulation, whereas a low value may indicate the presence of faults or moisture ingress.

Applications and Advantages

Megger testing finds widespread application in assessing the insulation integrity of electrical cables, motors, switchgear, and other components. It is instrumental in identifying potential weaknesses before they escalate into costly failures, thereby enhancing system reliability and safety. Moreover, Megger testing can be performed quickly and non-destructively, making it a preferred choice for routine maintenance and troubleshooting activities.

Key Differences and Comparative Analysis

While both Tan Delta and Megger tests aim to evaluate insulation integrity, they differ significantly in their operating principles, applications, and sensitivity to certain types of faults. Here’s a comparative analysis highlighting their distinct features:

AspectTan Delta TestMegger TestPrincipleMeasures dielectric dissipation factor (δ)Measures insulation resistanceFrequencyTypically conducted at high frequency (kHz)Utilizes DC voltage sourceSensitivityDetects subtle defects and moisture ingressIdentifies insulation resistance variationsApplicationCritical assets like transformers, generatorsElectrical cables, motors, switchgearDiagnosticProvides detailed insights into insulation conditionDetects presence of faults or moisture ingressMaintenanceEnables proactive maintenance strategiesFacilitates routine testing and troubleshooting

Conclusion

In conclusion, understanding the difference between Tan Delta Test and Megger Test is crucial for effectively assessing the insulation integrity of electrical systems. While Tan Delta testing offers unparalleled sensitivity to subtle defects and moisture ingress, Megger testing provides rapid and reliable assessment of insulation resistance. By incorporating both techniques into maintenance protocols, engineers and technicians can ensure the reliability, safety, and longevity of critical electrical assets.